INTRODUCTION

The Zeta Rod is a powerful device for maintaining water systems in a clean condition without causing corrosion. Even at high cycles of concentration the Zeta Rod keeps the condenser tubes and other surfaces free of scale with no chemical treatment. Corrosion levels measure well below target levels.

DATA COLLECTION AND RESULTS

A Zeta Rod System was installed on a new 50-ton evaporative condenser to evaluate corrosion on copper and soft steel coupons in the water downstream from the condenser. Studies of fouling, corrosion and water chemistry were conducted to qualify the Zeta Rod for widespread use in other cooling equipment installations at the college.

All tests were performed and data were collected and compiled independently by customer personnel, and corrosion measurements were conducted by an independent testing laboratory.

Measured Corrosion on Mild Steel and Copper.

Target maximum corrosion rates (Mils/year) - Mild Steel: 3.000 Copper: 1.000

Period
Number of Days
Cycles of
Concen-
tration
Blowdown TDS (mS) Mild Steel
Mils/year
Copper
Mils/year
Notes

18 Sept - 24 Oct
36 days

4 - 6

2400 - 3600

1.6855

0.1603

 

25 Oct - 4 Dec
40 days

8

4800

2.6799

0.0466

Some particles were noted on the coupon surfaces.

4 Dec - 15 Mar
101 days

8

4800

2.3433

0.0185

Some particles were noted on the coupon surfaces.

28 Mar - 4 Apr
33 days

8

4800

0.3908

0.1178

A fine mesh strainer was installed upstream of the coupons to remove particles.

30 Apr - 12 Jun 1997
43 days

12 - 16

7200 - 9600

0.1505

0.2545

 

SYSTEM DETAILS

Evaporative Condenser System: Frigidcoil 50-ton Model YEC-2-25
Average make-up water conductivity: 600mS
Zeta Rod System used: ZR18P (18" electrode), ZRPC Power Supply

SUMMARY

In this application, the cycles of concentration were taken to unusually high numbers. The unit is currently operating at 9 cycles of concentration without the use of any chemicals. To date, all surfaces of the unit are being kept free of scale and biofilm, while the corrosion levels are being kept well below the target levels. Additional Zeta Rod installations have been placed on the cooling tower, chillers, and plate-and-frame cooling systems at this location and the chemical water treatment system has been removed.